ProSoft PLX31-EIP-MBS模块
ProSoft PLX31-EIP-MBS模块
EtherNet/IP to Modbus Serial
PLX31-EIP-MBS
ProSoft Technology’s EtherNet/IP™ to Modbus® Serial communication gateway allows high-speed bi-directional data transfers between EtherNet/IP™ PACs or devices and Modbus®-enabled PACs or devices.
EtherNet/IP™ PACs include Rockwell Automation® ControlLogix® and CompactLogix™, as well as several Schneider Electric® controllers. Modbus® Serial devices are widely used in nearly every industry and include SCADA systems and Power Monitors.
The gateway includes several features that allow for simplified integration, reduced commissioning time and optimized performance
※※※ 深圳市扎克贸易有限公司
※※※ 张瑞 188-24-24-3080(V同)
※※※ Q:306-167-1820
Specifications
EtherNet/IP™ Specifications
Specification | Description |
Number of Class 3 Server Connections | 5 |
Supported PLC Types | PLC2, PLC5, SLC, CLX, CMPLX, MICROLX |
Supported Message Types | PCCC and CIP |
Class 3 Client Connections | Connected: 2 |
Number of Class 1 I/O Connections | 2 |
I/O connection sizes | 248/248 |
Max RPI time | 5 ms per connection |
CIP Services Supported | 0x4C - CIP Data Table Read |
Command List | Support for 100 commands per Client, each configurable for command type, IP address, register to/from addressing and word/bit count. |
Command Sets | PLC-2/PLC-3/PLC5 Basic Command Set |
Modbus Serial Specifications
Specification | Description | ||
Command List | Up to 100 commands per Master port, each fully configurable for Function Code, slave address, register to/from addressing and word/bit count. | ||
Supported Modbus Function Codes | 1: Read Coil Status | 15: Force (Write) Multiple Coils | |
Software configurable communication parameters | Baud rate: 110 baud to 115.2 kbps Parity: None, Even, Odd Data Size: 7 or 8 bits Stop bits: 1 or 2 RTS on/off delay: 0 to 65535 milliseconds | ||
Polling of Command List | Configurable polling of command list, including continuous and on change of data, and dynamically user or automatic enabled. | ||
Status Data | Error codes available on an individual command basis. In addition, a slave status list is maintained | ||
Node Address | 1 to 247 (software selectable) | ||
RS Interface | RS232, RS422, and RS485 | ||
Transmit and Receive Buffer Size | 255 byte Transmit character length with 0 to 65535 millisecond delay between each transmitted character |